Chevron Fire Foam Test Held Spring
2001
3% Premix – Type III – 93 Octane Gas – 0.06 gpm / sq ft Application
Rate
|
Test
# |
Concentrate |
Control |
Extngshmnt |
First Torch* |
Second
Torch** |
10
sq ft Burnback Test |
|
|
Area
[sq ft] |
Notes |
||||||
|
16 |
Verde Environmental, Inc.:
|
1:43 |
2:33 |
NO IGNITION |
NO IGNITION |
Self- Extngshmnt |
Walkover 14:00 – 14:55. Self-extngshmnt at 14:55. |
|
15 |
National
Foam : |
1:50 |
2:30 |
NO
IGNITION |
NO
IGNITION |
Self-
Extngshmnt |
Walkover
14:00 – 15:45. Self-extngshmnt
at 15:45. |
|
10 |
Ansul:
|
2:03 |
2:44 |
NO |
NO |
Self- |
Walkover
14:00 – 15:06. Self-extngshmnt
at 15:06. |
|
12 |
Buckeye
Foam: Buckeye 3%-3% AR-AFFF (BFC-33) |
1:52 |
2:46 |
NO
IGNITION |
NO
IGNITION |
Self-
Extngshmnt |
Walkover
14:00 – 15:42. Self-extngshmnt
at 15:42. |
Notes:
*:
First torch was conducted between 4:30 and 5:30 for all tests.
**: Second
torch was conducted between 11:00 and 11:50 for all tests.
The following manufacturers / products FAILED the above testing:
| Copyright © 2006 Verde Environmental, Inc. Contact us concerning this web page. |